System Design Atlas
Application system

Sensor monitoring with late measurements

Record room temperatures transparently, display time series and create temperature alerts that can be reviewed.

Follow the design
Temperature sensor with a rising measurement curve.

Participants and responsibilities

People, devices and operations

The building team evaluates alerts in their building context. Device operations investigates device time, connectivity and assignment. Platform operations manages the data path, storage and recovery.

  • Building team

    Reviews a temperature alert in its room context, acknowledges it and arranges any physical action outside the system.

  • Device operations

    Assigns devices and investigates connectivity, boot sessions and suspicious device times.

  • Platform operations

    Monitors measurement ingestion, processing backlogs, progress, storage and platform recovery.

  • Device gateway

    Transmits measurements and may resend a message. The system therefore detects duplicates itself.

Workflow in detail

From measurement to reviewable temperature alert

Each step shows the action of the person, the task of the system and the achieved result.

  1. Assign devices

    Action
    An assigned device measures room temperature and sends the value, boot session, sequence number and measurement time.
    What the system does
    Checks device key and assignment and stores the raw value so that a repetition is detected.

    Result: A durably traceable raw measurement exists, or quarantine records why it was withheld.

  2. Accept measurements

    Action
    The gateway receives an ingestion acknowledgement or resends the measurement after a connection failure.
    What the system does
    Recognises identical content as a retry. Different content with the same identifier goes into quarantine.

    Result: A repeated transmission generates at most one stored measured value.

  3. Check raw value

    Action
    The system processes accepted raw measurements from the last saved checkpoint.
    What the system does
    Assigns each measurement to a time window of 60 seconds using measurement time and marks the window as open or provisional.

    Result: The window contains a traceable, provisional assessment.

  4. Form time windows

    Action
    The fixed waiting time of 120 seconds after the end of the time period has been reached.
    What the system does
    Finalises the assessment using raw measurements processed before the cutoff and atomically stores the count, applied rule version and finalisation time. Processing delays do not move the cutoff.

    Result: The final mean is traceable and stable.

  5. Evaluate alerts

    Action
    Four different valid measurements give an average of 30.5 °C after completion of the evaluation.
    What the system does
    Opens a temperature alert and provides its history, measurement count and applied rule version.

    Result: A reviewable temperature alert is open; it provides no automated hazard prevention.

  6. Provide history and next actions

    Action
    The building team acknowledges the alert and continues to follow the temperature history.
    What the system does
    Saves the acknowledgement. Resolution requires a newer final time window with at least four distinct valid measurements and a mean of at most 30 °C. A data gap is insufficient.

    Result: Acknowledgement and resolution remain separate.

Workflow variations

Clear reactions to deviations

Duplicate, late and suspiciously timed measurements receive a visible status and an assigned next action.

Duplicate delivery after reconnect

The same measured value with the same identifier and the same contents reappears.

Reaction
The system acknowledges the stored measurement and creates no second raw measurement or alert.
Result
The curve contains the measured value exactly once, even though the transmission was repeated.

Delayed value after closure

By measurement time, a raw value belongs to an already final window, but it arrives at the platform later.

Reaction
The system stores and identifies the raw value as delayed and shows it as information about the data quality.
Result
The historical mean and any resulting temperature alert remain unchanged.

Device time is in the future

The measurement time and the reception time deviate beyond the defined diagnostic limit.

Reaction
The system quarantines the value with a specific reason; device operations checks its clock, assignment or firmware.
Result
The value has no effect on a time window and remains traceable for investigation.
Open design steps