System Design Atlas

Building digital twin with controlled equipment actions

02 / 10Worked example

Verifiable requirements

Check measurement age and control range together. Which conditions permit authorisation?

60% can be inadmissible when the measurement is stale.

Starting point Explicit control authorisation separates simulation from physical effect.

Assumptions for the example case

A fictional laboratory setup with a ventilation demonstrator. Local hardware limits operate independently; this example replaces neither building automation nor a safety function. All quantities, thresholds and operational targets in this design are illustrative assumptions.

Authorisation windows

Three authorisation checks

Proposal S-4260 % on revision 4
Age < 30 s?No → age rejected
Mapping valid?No → mapping rejected
20 ≤ setpoint ≤ 80?No → limit rejected
AuthorisedAll three checks
Vorschlag S-42 → Alter < 30 s?M-42
Alter < 30 s? → Zuordnung gültig?Yes
Zuordnung gültig? → 20 ≤ Soll ≤ 80?Yes
20 ≤ Soll ≤ 80? → FreigegebenYes

Each gate has its own reason for rejection; 20 and 80 percent are included.

Three checks: age<30 s, 20≤target≤80 and valid mapping. Each rejection has a separate outcome.

Business requirements (functional)

Further reading
Rule 1
Simulation never writes directly to the controller.
Rule 2
Control authorisation requires a measurement age <30 s, a valid mapping and a setpoint within the inclusive range 20..80 %.
Rule 3
An unknown effect remains unresolved; only matching controller confirmation completes the command as Applied.

Quality goals (non-functional)

Further reading
Measurement window
95% of local authorisation checks complete within 300 ms at 20/s over 15 min; measure controller response separately. Reconciliation begins from 5 seconds without a response.
Open results
Applied and Not executed require controller evidence; Rejected requires local validation reasons. Building operations retains responsibility for unresolved effects.

Check data age and the permitted control range together.

Check data age and the permitted control range together.

Age<30 s and 20..80 % must both hold.

60% can be inadmissible when the measurement is stale.

29,999 ms allowed; 30,000 ms rejected. 81% is outside and is rejected despite fresh data.

Alternative considered
Checking only the setpoint ignores a stale measurement basis.
Trade-off
Current measurements can generate new waiting times.
Reassess
Other equipment requires its own limit profiles.

Try it yourself

Check 60% at 29,999 and 30,000 ms and 81% at 10 ms.

A hint for your attempt

60% can be inadmissible when the measurement is stale.

Compare with a possible solution
Age limit
29,999 ms allowed; 30,000 ms rejected.
Value limit
81% is outside and is rejected despite fresh data.

Apply to your project

What is the equivalent of checking data age and control limits together in your project?

Step 3: telemetry determines raw data volume. Which conditions guide capacity?